Northwestern University, Simpson Querrey Biomedical Research Center

Chicago, IL

Simpson Querrey Biomedical Research Center, exterior entrance, night

Overview

This new 12-story, 850,000-square-foot biomedical research laboratory in downtown Chicago is connected floor-by-floor to the Robert H. Lurie Medical Research Center. At the time of completion it was the largest biomedical academic research facility in the U.S. GBA commissioned the MEP/FP/specialty gas systems, including building facade windows, heat recovery chillers, and an array of 10 heat recovery wheels serving laboratory floors.

Simpson Querrey Biomedical Research Center, Commissioning

The Louis A. Simpson and Kimberly K. Querrey Biomedical Research Center of the Feinberg School of Medicine was designed with interconnected mechanical systems that work together to recover energy from typically energy-intensive laboratory spaces. This level of complexity provided the project team with many opportunities for interdisciplinary troubleshooting and office and field problem solving.

  • One area where commissioning-led review was particularly effective was in the operation of the heat recovery chillers and the hot water, chilled water, and medium-temperature chilled water systems that interact with them. The Cx process helped identify and resolve several issues during construction that would have significantly impacted building operation after occupancy.
  • The medium-temperature chilled water system typically draws its supply water from the chilled water return from the lab AHUs. The heat recovery chillers also draw water from the AHU chilled water return. During construction site walks, the commissioning team identified a piping design detail that would prevent these systems from operating together properly during cold-weather conditions when the AHU chilled water coils were closed.
  • After review with the design team and mechanical contractor, the medium-temperature piping connection was relocated further down the riser, on the other side of a check valve. Without these revisions, the heat recovery chillers would have lost flow during cold weather conditions, when chilled water valves for the AHUs were closed.
  • When verifying the operation of the overall chilled water system, and the interactions between the new chiller plant in a nearby building and the heat recovery chillers, the commissioning provider and the controls contractor identified system functional issues. These issues appeared during the transitions between heat recovery chillers-only operation and heat recovery and main chiller plant combined operation. A heat exchanger that interfaced between this plant and other buildings in the client’s campus was observed to have reversed flow in limited system conditions, leading to unintended and unstable operation.
  • GBA worked with the controls contractor to identify and confirm this action, then to devise and implement a fix. Working closely with the controls contractor, this system instability was resolved before it had a negative impact on chiller plant operations.
  • Through proactive actions and close working relationships among the commissioning team, the Simpson Querrey Biomedical Research Center opened as a more effectively and more efficiently operating building.
  • LEED Gold Certification was achieved.

View More Projects

Interested in learning more about how GBA can assist with your facility objectives? Our portfolio is a great place to start. 

Skyscraper board room

430 N. Michigan (Realtor Building)

A large-scale vertical expansion called on GBA's analytical, design, and commissioning skills.

Hallway with rehab equipment

Shirley Ryan AbilityLab, Pediatric & DayRehab Center

This outpatient center serves children and adults; GBA provided engineering design services for the adaptive reuse project.

Exterior of Todd Building, University of Kentucky

University of Kentucky, Lee T. Todd, Jr. Building

An ASHRAE Level 1 audit,  retro-commissioning, and a lab ventilation assessment improved sustainability.