Milwaukee Public Museum

Milwaukee, WI

Entrance, Milwaukee Public Museum.

Overview

This Wisconsin project involved systems investigation and design for a 150,000-square-foot public museum. GBA provided design for the replacement of air-handling units and distribution systems for exhibit space. The project also included analysis to determine the causes of negative pressurization of the building and of vibration problems that were affecting glass exhibit panels.

HVAC Upgrade Design

GBA analyzed the air-handling and exhaust systems to identify the causes of the building’s unwanted negative pressurization. Investigation revealed that the three largest AHUs (150,000-cfm total capacity) had variable frequency drives (VFDs) controlling supply fan speed to only 50% of full, while the associated return fans were operating at full speed and moving much more air than the supply fans. Adding VFDs to the return fan motors and reducing their speed eliminated the negative pressure condition and associated problems with garbage odors on the first floor. GBA also designed the replacement of steam humidifiers for these three AHUs.

GBA also investigated the source of vibration that was causing the exhibits’ glass panels to vibrate excessively. The AHUs with the reduced fan speed had supply fan base vibration isolators that had been improperly selected and installed, allowing the supply fan bases to come in contact with the concrete pad supporting the fans. Replacing the vibration isolators eliminated the vibration of the glass.

In addition, GBA designed the lighting, cooling, heating, and ventilation systems associated with remodeling of 5,000 square feet of floor space for new exhibit space and a new education area. Two new AHUs provide cooling and ventilation for the remodeled areas. The AHUs were selected to allow these areas to be served by the two units operating separately or together, or for both to be served by one AHU, depending on occupancy.

View More Projects

Interested in learning more about how GBA can assist with your facility objectives? Our portfolio is a great place to start. 

Skyscraper board room

430 N. Michigan (Realtor Building)

A large-scale vertical expansion called on GBA's analytical, design, and commissioning skills.

Hallway with rehab equipment

Shirley Ryan AbilityLab, Pediatric & DayRehab Center

This outpatient center serves children and adults; GBA provided engineering design services for the adaptive reuse project.

Exterior of Todd Building, University of Kentucky

University of Kentucky, Lee T. Todd, Jr. Building

An ASHRAE Level 1 audit,  retro-commissioning, and a lab ventilation assessment improved sustainability.