- Zone pressure control was achieved by adding zone pressure differential sensors between the separate fire zones, adding variable frequency drives to the exhaust fans, and upgrading the local building automation controllers.
- The systems can now modulate variable frequency drives based on measured pressure differentials in the space.
- Sheet metal modifications to improve system balancing were specified, including the addition of manual volume dampers to existing exhaust ducts.
- Architectural improvements to the building exterior wall included sealing of holes in walls and specification of tighter exterior doors to reduce the infiltration and improve space temperatures.
- In addition to the design, GBA provided final system commissioning via functional performance testing.
Search For:



